Legislation Details

File #: 15-10466    Version: 1
Type: Code Violation Status: New Business
File created: 6/9/2026 In control: Special Magistrate
On agenda: 6/24/2026 Final action:
Title: FIRE-037-2026 A & B Property Address: 1200 Deltona Boulevard, Deltona, FL 32725 Parcel ID: 8130-06-00-0020 Property Owner: Deltona Wellness LP P.O. Box 280 Lawrence, NY 11559-0280 Violation: A City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 8.1.2.1 – Upblast fans with motors surrounded by the airstream shall be hinged and supplied with flexible weatherproof electrical cable and service hold-open retainers. Corrective Action: Please contact your hood service provider to install a hinge kit on your kitchen exhaust fan. Violation: B City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 96, CH. 8.14.7 – Exhaust fans shall have a drain directed to a readily accessible and visible grease receptacle not to exceed 1 gal (3.8L). Corrective Action: Please contact your hood service provider to install a grease box on your ki...