<?xml version="1.0" encoding="utf-8"?><rss version="2.0" xmlns:atom="http://www.w3.org/2005/Atom"><channel><title>City of Deltona - File #: 15-10464</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8065862&amp;GUID=F802E61D-F0F5-4FE2-BE29-8425B133E360</link><description /><generator>Legistar</generator><ttl>15</ttl><atom:link href="https://deltona.legistar.com/Feed.ashx?GUID=F802E61D-F0F5-4FE2-BE29-8425B133E360&amp;ID=8065862&amp;M=LD" rel="self" type="application/atom+xml" /><item><title>City of Deltona - File #: 15-10464</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8065862&amp;GUID=F802E61D-F0F5-4FE2-BE29-8425B133E360</link><guid isPermaLink="false">F802E61D-F0F5-4FE2-BE29-8425B133E360-2026-06-10-19-48-15</guid><description>Title: FIRE-033-2026 A - G
Property Address:
1251 Providence Boulevard, Suite 101, Deltona, FL 32725
Parcel ID: 8132-01-01-0050
Property Owner: 
Obsidian ML 8 LLC.
11995 EL Camino Real
San Diego, CA 92130-2539

Violation: A
City of Deltona Ordinance,Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.7.3.1 – Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification of the circuit source that supplies the disconnecting means. The marking shall be of sufficient durability to withstand the environment involved. [70:110.22(A)] 

Corrective Action:
Please label each disconnecting means (breakers) to indicate its function on the panel schedule. [1:11.1.7.3.1] 

Violation: B
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.4.2 – The re locatable power taps shall be d</description><pubDate>Wed, 10 Jun 2026 19:48:15 GMT</pubDate></item></channel></rss>