<?xml version="1.0" encoding="utf-8"?><rss version="2.0" xmlns:atom="http://www.w3.org/2005/Atom"><channel><title>City of Deltona - File #: 15-10466</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8065176&amp;GUID=E8668BD1-D113-4534-B81E-B7000FB54F5E</link><description /><generator>Legistar</generator><ttl>15</ttl><atom:link href="https://deltona.legistar.com/Feed.ashx?GUID=E8668BD1-D113-4534-B81E-B7000FB54F5E&amp;ID=8065176&amp;M=LD" rel="self" type="application/atom+xml" /><item><title>City of Deltona - File #: 15-10466</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8065176&amp;GUID=E8668BD1-D113-4534-B81E-B7000FB54F5E</link><guid isPermaLink="false">E8668BD1-D113-4534-B81E-B7000FB54F5E-2026-06-10-19-48-15</guid><description>Title: FIRE-037-2026 A &amp; B
Property Address:
1200 Deltona Boulevard, Deltona, FL 32725
Parcel ID: 8130-06-00-0020
Property Owner: 
Deltona Wellness LP
P.O. Box 280
Lawrence, NY 11559-0280

Violation: A
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 8.1.2.1 – Upblast fans with motors surrounded by the airstream shall be hinged and supplied with flexible weatherproof electrical cable and service hold-open retainers.

Corrective Action:
Please contact your hood service provider to install a hinge kit on your kitchen exhaust fan.

Violation: B
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 96, CH. 8.14.7 – Exhaust fans shall have a drain directed to a readily accessible and visible grease receptacle not to exceed 1 gal (3.8L). 

Corrective Action:
Please contact your hood service provider to install a grease box on your kitchen exhaust fan. 

Fire Safety Inspector Ajorie Bailey</description><pubDate>Wed, 10 Jun 2026 19:48:15 GMT</pubDate></item></channel></rss>