<?xml version="1.0" encoding="utf-8"?><rss version="2.0" xmlns:atom="http://www.w3.org/2005/Atom"><channel><title>City of Deltona - File #: 15-10368</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=7973462&amp;GUID=5FB96D79-8207-4EB1-84F7-400FE08C4010</link><description /><generator>Legistar</generator><ttl>15</ttl><atom:link href="https://deltona.legistar.com/Feed.ashx?GUID=5FB96D79-8207-4EB1-84F7-400FE08C4010&amp;ID=7973462&amp;M=LD" rel="self" type="application/atom+xml" /><item><title>City of Deltona - File #: 15-10368</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=7973462&amp;GUID=5FB96D79-8207-4EB1-84F7-400FE08C4010</link><guid isPermaLink="false">5FB96D79-8207-4EB1-84F7-400FE08C4010-2026-04-09-13-38-30</guid><description>Title: FIRE-019-2026
Property Address:
1235 Providence Boulevard, Deltona, FL 32725
Parcel ID: 8130-05-06-0010
Property Owner: 
Deltona Commercial Group LLC. 
935 N. Beneva Road STE 101
Sarasota, FL 34232-1399

Violation: A
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 11.1.7.3.1 – Identification of Disconnecting Means. Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification of the circuit source that supplies the disconnecting means. The marking shall be of sufficient durability to withstand the environment involved. [70:110.221(A)] 

Corrective Action:
Please relabel the electrical disconnects for Suites M and N.

Violation: B
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. - Adopted Florida Fire Prevention Code 8th Edition, NFPA 1, 11.1.8 – Covers. All panelboard and switchboards, pull boxes, junctio</description><pubDate>Thu, 09 Apr 2026 13:38:30 GMT</pubDate></item></channel></rss>