<?xml version="1.0" encoding="utf-8"?><rss version="2.0" xmlns:atom="http://www.w3.org/2005/Atom"><channel><title>City of Deltona - File #: 15-10408</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8004871&amp;GUID=520BE6DA-8A2C-49A1-98CC-0F1DAF1077D1</link><description /><generator>Legistar</generator><ttl>15</ttl><atom:link href="https://deltona.legistar.com/Feed.ashx?GUID=520BE6DA-8A2C-49A1-98CC-0F1DAF1077D1&amp;ID=8004871&amp;M=LD" rel="self" type="application/atom+xml" /><item><title>City of Deltona - File #: 15-10408</title><link>https://deltona.legistar.com/Gateway.aspx?M=LD&amp;From=RSS&amp;ID=8004871&amp;GUID=520BE6DA-8A2C-49A1-98CC-0F1DAF1077D1</link><guid isPermaLink="false">520BE6DA-8A2C-49A1-98CC-0F1DAF1077D1-2026-05-06-20-28-45</guid><description>Title: FIRE-028-2026
Property Address:
1240 Providence Boulevard, Deltona, FL 32725
Parcel ID: 8130-05-47-0420
Property Owner: 
Chulli Corp. 
920 Grand Hilltop Drive
Apopka, FL 32704

Violation: A
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH. 11.1.7.3.1 – Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification of the circuit source that supplies the disconnecting means. The marking shall be of sufficient durability to withstand the environment involved [70:110.22(A)]. 

Corrective Action:
Please indicate suite served by each electrical disconnect and label the large electrical disconnect to indicate it’s purpose.

Violation: B
City of Deltona Ordinance, Chapter 42, Article IV, Fire Codes, Ch. 42-186. – Adopted. Florida Fire Prevention Code 8th Edition, NFPA 1, CH 11.1.8 - All panelboard and switchboards, pull boxes, junction</description><pubDate>Wed, 06 May 2026 20:28:45 GMT</pubDate></item></channel></rss>